Climatix Heating System Library

The Climatix Air System extension installs a set of libraries that are available at the following path: Libraries > L1-Headquarter > BA > Device > BA_Heating_Climatix_150_HQ_1.

Graphic Templates

The document Climatix DH BACnet Objects CE1Z2912en states that the Climatix application DH includes predefined monitoring and control function components for monitoring district heating systems.

The following schemas give an overview of selectable measured values and control equipment for the main functions composing a DH application.

Pre-Controller Circuit
Heating Circuit
Domestic Hot Water With Internal Heat Exchanger
Domestic Hot Water with External Heat Exchanger
Domestic Hot water Without Storage Tank

The above Climatix DH components are graphically provided in the Desigo CC graphic templates representing the Climatix DH system. The Climatix Heating System extension provides the graphic templates described below.

Climatix_DH_01_None_None_001_150 Graphic Template

This graphic template can cover the full District Heating application composed by 3 x Pre-Controller circuits, 4 x Heating circuits and 3 x Domestic Water. The Solar components, introduced with version 1.20, are not yet represented in graphic templates.

Values and Control Equipment, as Provided by the Desigo CC Graphic Template Climatix_DH_01_None_None_001_150

This template provides the best functionalities when used in combination with DH application version 1.20, where specific BACnet objects are provided to allow the template to be very dynamic and capable to cover a wide range of application configurations. With this template, the heating groups and domestic hot water circuits are dynamically moved to the appropriate pre-controller segment based on the configuration. Also, they are directly connected to the main circuit in case pre-controllers are not used. The BACnet objects used for segments assignments are the following:

  • HG1HDstSegm: Indicates to which segment the Heating Group 1 is assigned.
  • HG2HDstSegm: Indicates to which segment the Heating Group 2 is assigned.
  • HG3HDstSegm: indicates to which segment the Heating Group 3 is assigned.
  • HG4HDstSegm: Indicates to which segment the Heating Group 4 is assigned.
  • DW1HDstSegm: Indicates to which segment the Domestic Hot Water 1 is assigned.
  • DW2HDstSegm: Indicates to which segment the Domestic Hot Water 2 is assigned.
  • DW3HDstSegm: Indicates to which segment the Storage Tank 3 is assigned.

These BACnet objects are configured in the Climatix controller with the correct value to identify the appropriate segment where the components is linked. The values and meaning of the values for these points are the same for all the listed BACnet objects:

1 = Direct connection (no PreController)

- 2 = PreController 1

3 = PreController 2

- 4 = PreController 3

Scenarios like shut off valves in the pre-controllers or multiple domestic hot water circuits connected to the same line are also covered when using DH application v1.20.

This template is associated to the function ClimatixDH_01_150.

Climatix_DH_02_None_None_001_150 Graphic Template

The maximum configuration of this template comprises 3 x pre-controller circuits, 3 x heating circuits and 1 x domestic water circuit.

Values and Control Equipment, as Provided by the Desigo CC Graphic Template Climatix_DH_02_None_None_001_150

This template is associated to the function ClimatixDH_02_150.

 

Functions

The functions provided with the library are used to represent the Climatix District heating unit in Desigo CC and their properties provide the most important information about the device. The function is also the entity where the graphic template is associated. Therefore, configuring a function for a Climatix controller automatically results in the graphic template linked to this function associated to the DH controller. For an overview of the graphic templates and the associated functions, see Graphic Templates.

The following are the properties available in the functions Climatix_DH_01_150 and Climatix_DH_02_150.

Property Name

Property Description

Summary Status

Summary Status

CmnHtmHCap

Power

CmnHtmHEg

Cumulated energy

CmnSeason

Su/Wi switch

CmnHtmFl

Flow

CmnHtmTFl

Flow temp. heat meter

CmnHtmTRt

Return temp. h. meter

CmnHCnsMgtHDmdPcVal

Heat demand value

CmnAlmAx

Auxiliary alarm

CmnManIO

IO handoperated

CmnSched

Time schedule common

HG1Sched

Time schedule HC1

HG2Sched

Time schedule HC2

HG3Sched

Time schedule HC3

HG4Sched

Time schedule HC4

DW1Sched

Time schedule DW1

DW2Sched

Time schedule DW2

CmnHCnsMgtHDmdVld

Heat demand

CmnOpMod

Main operating mode

CmnOpSta

Operating state

DW3Sched

Time schedule DW3

CmnHtmHCap

Power

CmnHtmHEg

Cumulated energy

CmnSeason

Su/Wi switch

BACnet Auto Discovery Rules

Part of the library installed with the Climatix Heating System extension is also the Climatix DH discovery rules where the BACnet objects exposed by the Climatix DH application are mapped to the designed Desigo CC functions.

Climatix DH Discovery Rules

 

Dependencies

The Climatix Heating System extension is configured to depend on the following extension, which will be automatically added, if it is not already installed in the system, when the Climatix Heating System extension feature is selected: