Integrating Notifier ID3000

Scenario: You want to configure Desigo CC for connecting to the NOTIFIER® ID3000 fire panel.

 

Reference: For background information, see the reference section.

 

Workflow diagram:

 

 

Prerequisites:

  • The Notifier ID3000 extension is installed and included in the active project.
  • You prepared the configuration (CSV) file for the NOTIFIER® ID3000 fire panel you want to integrate. See Notifier ID3000 Configuration (CSV) File.
  • System Manager is in Engineering mode.
  • System Browser is in Management View.

 

Steps:

1 – Create the Modbus Driver
  1. Depending on where the driver will run, select one of the following:
  • Project > Management System > Servers > Main Server > Drivers
  • Project > Management System > FEPs > [FEP station] > [drivers folder]
    NOTE:
    If the [drivers folder] is not available, to create it select the [FEP station] and click New .
  1. In the Object Configurator tab, click New and select New Modbus Driver.
  1. In the New object dialog box, enter a description and click OK.
    NOTE: To avoid difficulties and mistakes in choosing the driver in multi-selection lists, do not use the same description on the Desigo CC server and FEP stations.
  • The newly created Modbus driver is added to System Browser, but not started.

 

2 – Create the Modbus Network
  1. Select Project > Field Networks.
  1. In the Object Configurator tab, click New and select New Modbus Network.
  1. In the New Object dialog box, enter a name and description, and click OK.
  • The newly created Modbus network is added to System Browser.

 

3 – Associate a Driver to the Modbus Network
  1. Select Project > Field Networks > [Modbus network].
  1. In the Modbus tab, open the Network Settings expander.
  1. From the Monitored by driver drop-down list, select the driver.
  1. Click Save .

 

4 – Start the Modbus Driver

The status of a newly created driver is Stopped. To be able to connect, the driver must be started with either Start or Start Conf…

  1. Select Project > Management System > Servers > Main Server > Drivers > [Modbus driver].
  1. In the Extended Operation tab, click Start.
    NOTE: Only for configuration purposes, you can also click Start Conf… to activate the driver without establishing any real connection to the field.

 

5 – Import the Configuration
  • To speed configuration, make sure the Desigo CC Transaction Mode is set to Simple or the Automatic Switch of Transaction Mode is set to True.
    The automatic switch setting is recommended. Without it, to re-enable the logs, you need to set the Transaction Mode to Logging at the end of the configuration procedure.
  1. Select Project > Field Networks > [ID3000 network].
  1. In the Import tab, click Browse.
  1. In the Open dialog box, navigate to and select the device configuration file (CSV) and click Open.
  • By default, data structures are imported into Management View.
  1. (Optional) To check the pre-import log, click Analysis Log.
  • The Analysis Log dialog box displays its outcome that you can also save in a .txt file.
  1. (Optional) In the Hierarchies Mapping expander, define destination in other system views of the data structures (hierarchies contained in the configuration file). The suggested field indicates the correct view root to link for each specific hierarchy. To assign each hierarchy to a destination view, proceed as follows:
    a. Select the Manual Navigation check box to retain the Import tab.
    b. In System Browser, select the optional view (logical view or user-defined view).
    c. Drag the optional view root node from the System Browser tree to the suggested field.
    NOTE: The hierarchies mapping configuration cannot be modified after the import of the configuration file. For general background information about the Desigo CC import feature and Desigo CC views, see Field Data Import and Views.
  • The hierarchies settings configured are activated and will be applied during the configuration import.
    NOTE: If you configure the hierarchies mapping, and the [Logical Hierarchy] and [User Hierarchy] fields are not defined in the CSV configuration file, data structures will not be imported into the logical view and user-defined view.
  1. To transfer the interfaces to import from the Source Items list to the Items to Import, click .
  1. (Optional) Select the Delete unselected items from the Views check box to remove from the views—during the import—any items that are not present in the file to import.
  1. Click Import.
  • The Import tab displays the Import in progress page.
  • The Cancel button becomes available and allows you to stop the procedure at any time. In this case, a summary of the partial results is provided.
    NOTE: No rollback function is available. This means that canceling the import may result in an inconsistent state of the system database.
  • When the import completes, the imported configuration data structures are added to System Browser.
  1. (Optional) To view a summary of the import, click Import Log.
  • The Import Log dialog box displays its outcome that you can also save in a .txt file.

 

6 – Finish the Configuration