Configure Building X Connector

  • System Manager is in Engineering mode.
  1. De-select Manual Navigation.
  1. Select Project > Management System > Servers > Main Server > Building X Connector.
  1. Select the Building X Connector tab.
  1. Click Edit .
  1. Do the following:
  • For Software User, click the drop-down arrow, and then select the user you created earlier—for example, Building X User.
  • For Discovery View, click the drop-down arrow, and then select the view you created earlier—for example, Building X View.
  1. Click Save .
  • After several seconds, the Operational State displays Ready.
  1. In the Building X Connector tab, expand Building X Preview.
  1. Click Discover.
  • An expandable list of devices and points, along with a count of devices and points, displays in the Building X Preview expander.

  1. Verify that the listed devices and points are consistent with your expectation.
  1. Click Upload, and then click OK.
    NOTE: the upload button is disabled if Desigo CC and Building X are aligned (have no differences).
  • All devices and points in the preview area are uploaded to Building X.
  1. Using a Building X application—for example, Operations Manager—verify that devices and points were uploaded.
    NOTE: You will need access to a Building X application and its documentation.
  • In the Building X application—for example, Operations Manager—you can now monitor the current values and initiate commanding.